← All Logsheets
Formwork & Shoring
Pre-Pour Inspection Log
NYC BC §3303.7 · ACI 347.2R · Concrete Safety Manager Required · BC §3301.9.2
PL-016
Project Address
General Contractor DOB Job No.
SSM Name SSM License No.
CSM Name CSM License No.
Date of Pour Time of Inspection
Pour Location (Floor / Member) Est. Volume (CY)
Concrete Mix Design No. Specified f'c (PSI)
Approved Formwork Drawing No.
Formwork Design Compliance — ACI 347 / BC §3303.7YESNON/A
1Licensed PE-stamped formwork and shoring design documents present on site and reviewed with field crew prior to work
2Formwork designed for full concrete dead load plus minimum 50 psf construction live load
3Shore spacing and layout matches approved drawings — no field modifications without PE approval
4Reshoring plan reviewed; reshored floors below confirmed to carry combined design loads
Component Inspection — ACI 347.2RYESNON/A
5All form panels, decking, and wales in good condition — no excessive bow, splits, or rot
6Shore legs plumb; base plates bearing on firm surface — no shoring on asphalt or soft fill
7Adjustable screw jacks set within allowable extension range — thread exposure does not exceed manufacturer's published limit
8Horizontal bracing and cross-bracing installed per drawings; all connections fully secured
9Base lift-off plates and wedges fully engaged; all form tie rods, bolts, and locking pins in place
10All openings, sleeves, and embeds properly formed, positioned, and secured
Day-of-Pour ChecklistYESNON/A
11Reinforcing steel placed per structural drawings; lap splices, cover, and clearances confirmed
12Conduit, sleeves, and embedded items secured — will not shift during vibration
13Concrete delivery tickets match approved mix design; test cylinder samples prepared
14Concrete pump line or discharge chute placed so that no individual form panel or shore bears load beyond design capacity
15Vibration procedure discussed with crew — no over-vibration near form ties or edges
16Contingency shoring materials on site — spare shores, base plates, wedges, and screw jacks available for emergency use
Deficiencies & Corrective Actions — All items must be resolved before pour commences

"By signing below, I certify that the formwork and shoring have been inspected and, in my professional judgment as the responsible safety professional, are prepared for concrete placement in accordance with approved drawings and applicable codes."

SSM Name (print)License No.
SSM SignatureDate & Time
CSM Name (print)License No.
CSM SignatureDate & Time